NOTE: ALL safety requirements as indicated by warning symbols in manual must be met.
Verify ALL Turbine disconnects (including the Service Disconnect Box) open the brake control wire (SR5)
· AC Power OFF to Turbine controller and Inverters
· Place ALL Disconnect Switch in the ON position
· Measure Resistance from SR5 to SR6 Terminals disconnected at Turbine controller
o (Resistance MUST be between 6 -12 ohms)
· Measure Resistance from SR7 to SR8 Terminals disconnected at Turbine controller
o (This MUST be OPEN)
· For the Disconnect UNDER TEST, Place the Switch in the OFF position
· Measure Resistance from SR5 to SR6 Terminals disconnected at Turbine controller
o (This MUST be OPEN)
By typing your name in this document, you are signing and verify that information is correct and acknowledge that you are responsible for corrective action to bring the system to the requirements of the manual. You also acknowledge that you are responsible for at least one return visit should it be required.